The series AVG averaging temperature sensor can be used to measure the average temperature up stream of the cooling coils in an air handler
The coiled sensor unwinds to a length of 12 or 24' to take an average temperature reading across a large space
The housing has multiple knockouts to reduce the time to install conduit
The series CC1 mounting brackets can be used to secure the capillary to the wall of the air handler without kinking
The series AVG can be ordered with a choice of 11 output options that allow it to communicate to any standard building control system
Specifications:
Accuracy: platinum RTD: ±0.6% at 32°F (0°C), nickel RTD: ±0.5°F at 32°F (0°C), Balco RTD: ±0.1% at 32°F (0°C), thermistors: ±0.36°F from 32 to 158°F (0 to 70°C)
Operating temperature: -32 to 240°F (-35.5 to 115.5°C)