    Heptafluoropropane gas fire extinguishing equipment
    Share this page
    Production Lead Time:
    30 day(s)
    Shipping Method:
    air, ocean
    Customised:
    Yes
    application:
    fire extinguishing system for data processing center, telecommunications facilities, computer room, process control center, expensive medical equipment, expensive industrial equipment, library, museum and art gallery, archives, emergency power facilities
    Description
    Contact Supplier
    Description

    Introduction:

    The HFC-227ea gas fire extinguishing system is a clean, environmentally friendly, and highly efficient fire suppression solution. It leaves no residue or corrosion after extinguishing a fire, offers excellent electrical insulation, and is based on well-established technology.

    Product categories:

        Cabinet-type (prefabricated) HFC-227ea gas fire extinguishing device

        Internal storage pressure (pipe network) HFC-227ea fire extinguishing system

        External storage pressure HFC-227ea fire extinguishing system

    System introduction:

    Fire extinguishing principle: It has both chemical and physical fire extinguishing effects, and has good fire extinguishing performance.

    Chemical fire extinguishing effect: It suppresses the development of fire by capturing free radicals and interrupting the chain reaction that causes flame propagation;

    Physical fire extinguishing effect: It absorbs a large amount of heat through molecular thermal motion to achieve the effect of cooling and cooling, and also has the effect of suffocating by reducing oxygen concentration.

    Application range: solid surface fire; liquid fire; gas fire that can cut off the gas source before extinguishing; electrical fire.

    Typical protection areas: data processing center, telecommunications facilities, computer room, process control center, expensive medical equipment, expensive industrial equipment, library, museum and art gallery, archives, emergency power facilities, oil-immersed transformer room, distribution room, generator room, etc.

    System classification: unit independent system, combined distribution system

    Technical Parameters:

    Storage pressure (20℃)
    2.5MPa
    4.2MPa
    5.6MPa
    Max working pressure (50℃)
    4.2MPa
    5.3MPa
    8.0MPa
    Operating temperature
    0℃~50℃
    Working voltage/current
    DC24V
    Fire extinguishing agent spraying time
    ≤10S
    Startup method

    Automatic/Manual

    Automatic/Manual/Mechanical emergency

    Maximum filling density (kg/m³)
    1120
    950