Please enter a valid keyword with 2 or more characters / numbers.
Introduction:
The high-pressure carbon dioxide fire extinguishing system is mainly composed of fire extinguishing agent bottle group, driving gas bottle group, one-way valve, selection valve, driving device, manifold, connecting pipe, nozzle, signal feedback device, safety release device, weighing device, low-leakage high-sealing valve, cylinder rack, etc., with carbon dioxide as the fire extinguishing medium.
System introduction:
Fire Extinguishing Principle: The system utilizes asphyxiation, cooling, and insulation to suppress fires. By releasing the fire extinguishing agent, the heat absorption from liquid carbon dioxide vaporization lowers the temperature of burning materials while reducing oxygen levels in the protected area.
Application Scope:
• Gas fires where the gas source can be cut off before extinguishing
• Liquid and liquefiable solid fires, such as paraffin and asphalt
• Surface and deep-seated solid fires, including cotton, fabrics, and paper
• Electrical fires
Typical Protection Areas:
Impregnation tanks, melting tanks, rolling mills, oil-immersed transformers, paint production lines, electrical aging rooms, coal powder silos in cement production, ship cabins, cargo holds, food warehouses, tobacco warehouses, cigarette warehouses, textile machines, and dust removal equipment.
System classification: Total flooding fire extinguishing system, local application fire extinguishing system
Technical Parameters:
| Storage pressure (20℃) | 5.7MPa |
| Max working pressure (50℃) | 12.4MPa |
| Operating temperature | 0℃~50℃ |
| Maximum filling density (kg/m³) | 600 |
| Total flooding spray time | surface fire: ≤1min; indepth frie:≤7min |
| Working voltage/current | DC24V, 1.4A |
| Startup method | Automatic/Manual/Mechanical emergency |